What should be considered when installing overhead data cabling?
Answer: A Next Question -
A data center is located in an area where the demand for power is higher than the utility power company is able to deliver. This results in frequent power outages and, therefore, power shedding(scheduled/controlled power shutdown for areas) is frequently applied. The mains power is more than 650 hours/year not available.What type of generators should be installed?
Answer: B Next Question -
A data center has its own power supply from the public utility and receives chilled water supply fromthe building owner.What needs to be taken into consideration when calculating the PUE?
Answer: C Next Question -
The humidity in the computer room has changed from about 50% down to 35% Relative Humidity (RH).What influence does this have on Electrostatic Discharge (ESD)?
Answer: C Next Question -
The 'maximum exposed area' of the fire-rated glass is defined by the supplier as 3 sqm/32 sqft. The window area is 4 sqm/43 sqft.What would be the best option?
Answer: C Next Question -
You are allowed to use a calculator for this question.A computer room has a net volume of approximately 2,500 m³ / 88,287 ft³. The temperature is 20 °C / 68 °F.The required design concentration is 7%.The S-Factor is 0.1359 (metric) / 1.885 (imperial).Calculate the amount of gas required for this computer room based on FM200. What is the correct weight?
Answer: B Next Question -
The temperature in the computer room is being increased from 18°C/64°F to 27°C/81°F.What is the impact, if any, on the amount of gas required to suppress a fire assuming the gas is a Halocarbon?
Answer: C Next Question -
What is a potential disadvantage of using water mist as a fire extinguishing system?
Answer: B Next Question -
A new network storage device in a non-standard size rack of approximately 600 kg/1,300 lbs is going to be installed in the data center.Are new floor loading calculations required?
Answer: D Next Question -
Which formula is correct?
Answer: B Next Question